  • What happens if line pressure is not written on the form?
  • If SOV2 is not leaking and the relief still won't open during RP testing, what is the next suspected component?
  • Which device is commonly used on a hose bib to prevent backflow?
  • Which device requires RPBA in-plant or premise for protection?
  • In an RP sequence, what is the function of check 2?
  • RPDA/DCDA protection adds what extra feature beyond RP/DCVA?
  • RP check-1 actual drop is too low. What is a likely component cause?
  • Which condition best describes a torn RP diaphragm?
  • Dirty / muddy water is which hazard class?
  • In booster pump configurations, what does siphonage upstream refer to?
  • Which statement describes a stabilized / steady-state gauge reading per CSA B64.10.1 Annex A?
  • What is a jumper, and is it allowed?
  • A heating boiler or pressure vessel that contains treatment chemicals is typically associated with which type of backflow?
  • What does RAG stand for in backflow terminology?
  • How many assessment factors are listed?
  • Can one physical connection produce either backpressure or back-syphonage?
  • True or false: an air gap cannot be bypassed.
  • Why is an engineer's liability defence hard?
  • During RP testing, what is the purpose of the TV1-to-TV4 jumper?
  • What does RPBA stand for in backflow terminology?
  • When can an honest error of judgment still be negligence?
  • 1 psi equals how many kPa?
  • Sight-tube conversion for 1 psi equals how many inches of water?
  • DCVA check-1 hookup?
  • Define backflow.
  • Which factor describes how dangerous a hazard is?
  • What is the required height for PVB / SRPVB above the flood level rim or the highest downstream piping?
  • In an RP backflow prevention sequence, what does check 1 do?
  • What is the critical level on a vacuum breaker?
  • Who must approve daylight drain installations before work begins?
  • DuC stands for which backflow device?
  • Which statement best describes back-syphonage?
  • Which statement about bypass around a backflow preventer is correct?
  • What is the required front clearance in an enclosure for a backflow device (excluding small units in removable boxes)?
  • What is the purpose of a cross connection control program?
  • In the designation DCAPC, what does the 'C' stand for?
  • Who is the water purveyor?
  • The jumper, swivel, change-over, and removable section are classed as what?
  • Where should the PVB check hose be connected and what action drains?
  • What is the minimum air-gap dimension for backflow prevention?
  • What is the minimum clearance below a boxed DCVA?
  • Which device includes two independent loaded checks, two shut-offs, and four test cocks?
  • What is the purpose of the air gap in the RP test?
  • During a PVB check pass, which valve remains closed?
  • Steam is which hazard class?
  • What is the clearance behind a typical assembly?
  • Who has direct responsibility to supply potable water to a premise?
  • After identifying the backflow type, which is the next consideration in the selection process?
  • During high hydrant flow, what happens in the main line?
  • Hose-bib with no hose attached — actual or potential? What type of backflow if a hose is added and the main breaks?
  • For a PVB air-inlet needle held at 0, which condition is most likely?
  • When a DCVA is installed in a pit, how should the test cocks be oriented?
  • During high hydrant flow, which phenomenon describes the effect on the system main?
  • DCVA pass criterion for DCVA check-1 uses which measurement to confirm proper function?
  • Which device is commonly used for beverage carbonators?
  • How tall is a barometric loop and what does it stop?
  • Residential hose-bib hazard and protection requires which hazard level and fixture protection?
  • RP relief discharge rule?
  • What is the minimum clearance below an RP centre-line or relief, given the relief opening above grade is at least 300 mm (12 in)?
  • When a bypass around a backflow preventer is installed, what level of protection must the bypass provide?
  • For an air gap near a wall within 3 pipe diameters, what change to the gap is required?
  • Which of the following premises is listed as High hazard: hospital, plating plant, marina, or car wash?
  • Lawn irrigation with chemical injection requires which hazard level and protection?
  • RP — What components are included in its assembly?
  • True or false: NBC / NPC rules only apply in provinces that adopted them.
  • A cross connection control program is designed to stop non-potable water from re-entering the public water supply.
  • What are the requirements for daylight drain from a semi-buried pit?
  • Which factor primarily drives the degree of hazard?
  • What is the flood level rim?
  • Can a device replace an approved cross-connection assembly?
  • Which designation indicates the Dual Check with Atmospheric Port without specifying a carbonator in the name?
  • What is the hold time required on every check test?
  • Which device stops back-siphonage only and is not designed for continuous pressure?
  • If the RP test indicates a leak after a downstream faucet is flushed, what is the recommended first diagnostic step?
  • Which device uses a bleed vent in place of the second test cock?
  • RP: you crack the low-side more than ¼ turn and the relief never opens. First check?
  • What does RP stand for in backflow terminology?
  • What does DCVA stand for in backflow prevention?
  • Which scenario is described as a moderate premise hazard?
  • What is backpressure?
  • Ice maker hazard and protection requires what level and protection?
  • When a DCVA is installed in a pit, what must be done with the test cocks?
  • What does purple pipe mean?
  • Garden sprayer / aspirator — type of backflow?
  • A tall building over 9.4 m (30 ft) is classified as which premise hazard?
  • For a PVB check pass, what condition is required after the body drains through TV2?
  • The centre-line height band for PVB / SRPVB / DCVA / RP is specified as which range above the floor?
  • Moderate hazard is associated with which description?
  • PVB stops what and is continuous-pressure capable?
  • What does a falling sight-tube column mean?
  • Approved air gap vs registered air gap?
  • True or false: once a bylaw exists, everyone is deemed to know it.
  • Fertilizer injector is which class of hazard?
  • Do temporary hydrant services require their own approved backflow preventer?
  • What is the front clearance requirement for typical enclosures?
  • What holds an RP relief valve closed?
  • What is back-syphonage?
  • Where is the PVB air-inlet hose connected, and how should the gauge be placed?
  • What is a stabilized / steady-state gauge reading?
  • Why might a PVB spit when SOV1 is opened for the first time?
  • What does AG stand for in backflow terminology?
  • Who has primary provincial responsibility for public health?
  • Submerged inlet — actual or potential? Type of backflow?
  • Which device is protected by DCVA as its backflow protection method?
  • How should a spitting RP relief be interpreted?
  • Is compressed-air blowout allowed on a PVB / SRPVB system?
  • Which of the following is a listed cause of RP dumping when you arrive?
  • What lawyer tactic names a pile of people after a backflow incident?
  • Define RP buffer.
  • In the RP test cocks sequence, which valve is closed last?
  • In a PVB air-inlet pass, when does the valve open?
  • Barometric loop stops which type of backflow?
  • Which device requires RPBA for protection with chemical injection?
  • An air gap stops which forms of backflow, what is the associated hazard level, and what is the recommended field-test approach?
  • SRPVB (SVBA) refers to which type of backflow device?
  • DCAP / DCAPC abbreviations refer to which backflow device, with the 'C' indicating carbonator?
  • What is the proper flush order for RP test cocks?
  • In an RP backflow sequence, what happens when the zone pressure climbs above the allowed margin below inlet?
  • RP restore order?
  • RP relief will not open when you crack the low-side. What is the first suspect?
  • Which abbreviation refers to a hose connection vacuum breaker?
  • Why can an RP relief spit on water hammer?
  • Which premise hazard level is associated with a sewage plant or sewage pump station?
  • RP hose hookup?
  • Bidet requires which hazard level and fixture protection?
  • Actual vs potential cross connection?
  • Is an extension ladder acceptable access for annual testing?
  • What are typical uses of DCAP and DCAPC?
  • Industrial hose-bib hazard and extra isolation is required to what level and protection?
  • What does AG stand for in backflow terminology?
  • May an RP be installed in a pit?
  • Which statement is true about air gap allowances near walls and corners?
  • The Ministry of Health holds primary provincial responsibility for public health.
  • In a PVB sequence, what happens when the inlet pressure falls and the air-inlet is loaded?
  • Should a potential cross-connection be treated the same as an actual cross-connection?
  • In a PVB air-inlet test, opening the bleed more than a quarter turn indicates what?
  • Chemical injector / fertilizer pump — type of backflow? How many extra CCs on that typical figure?
  • In a booster pump setup, what are the two backflow paths?
  • May you leave a spool in the line while parts are on order?
  • What is the purpose of RPDA/DCDA detector assemblies?
  • What is the term used for balancing cost against public safety?
  • CAN/CSA B64.10.1 is the standard used for testing backflow preventers.
  • Which water-borne disease is named by the self-test?
  • The notes warn against searching for which air-inlet value?
  • What is the first step in selecting a backflow prevention device?
  • Fire sprinkler, no additives requires which hazard level and protection?
  • The premise owner is responsible to maintain and test preventers on private property.
  • What distinguishes an assembly from a device in cross-connection control?
  • If closing SOV2 on an RP causes the relief to dump immediately, what is the first suspect?
  • The sight-tube conversion for 1 psi relates to which physical quantity?
  • When opening the RP bypass, a small needle dip occurs. How should this be interpreted?
  • Which device has the highest hazard described as severe with RPBA?
  • In an RP sequence, what does the relief do at no-flow?
  • AVB is the abbreviation for which backflow device?
  • AVB — what does it stop and what are its orientation and pressure limits?
  • Which device creates a physical separation to prevent backsiphonage?
  • What standard does Building Code Part 7 use for testing backflow preventers?
  • What is the centre-line height band for PVB / SRPVB / DCVA / RP above the floor?
  • Are on-site surveys needed if CSA tables exist?
  • Which option represents the Spill-Resistant backflow device?
  • What is the recommended AVB height above flood level rim?
  • Severe hazard is also called which term?
  • Where is HCVB/HFVB installed and what are its limitations?
  • If TV2 keeps running during the check test, what is the most likely fault?
  • What height above the flood level rim is the AVB recommended to be, according to the course guidance?
  • During DCVA testing, if TV3 runs while testing check 1, what is the first suspect?
  • Which device provides the highest level of protection against backflow in hazardous conditions?
  • True or false: almost anything but potable is some degree of hazard.
  • DCVA pass number for each check?
  • Bypass around a backflow preventer requires what level of protection?
  • In backflow prevention terminology, what does the abbreviation DCVA stand for?
  • What is the minimum hot-water temperature rating required for PVB / DCVA / RP installations?
  • Which matters more in assessment: toxicity or probability?
  • What is the correct order of the four RP test requirements?
  • What is the primary purpose of the second check in an RP backflow sequence?
  • Which item is not one of the four assessment factors?
  • Continuous vs non-continuous pressure?
  • According to the notes, 1 psid equals how many kilopascals?
  • Trap primer requires which protection mechanism?
  • Which assembly stops both BP and BS and is rated for moderate/minor hazard?
  • RP relief discharge method?
  • In the RP 2 psid rule, at what point must the relief open?
  • Fire sprinkler with chemical additives requires what hazard level and protection?
  • Which method of application protects the city main?
  • What is the most common reason DCVA checks leak?
  • HCVB / HFVB abbreviations refer to which type of backflow device used on hoses?
  • Bypass around a backflow preventer must have what level of protection?
  • What does a registered air gap imply in terms of inspection?
  • Contamination vs pollution?
  • Which factor describes how reliable the preventer is?
  • 1 inch equals how many millimeters?
  • What does purple pipe indicate in labeling schemes?
  • An RP relief opens too low. Which component issue is most likely?
  • RP premise isolation is often considered for which backflow category?
  • Severe hazard means?
  • During a DCVA test, if the sight tube shows the water receding, what is the issue?
  • Liability to an individual arises under what kind of law?
  • Domestic hot-water boiler, no chemicals requires which hazard and protection?
  • Is downstream shut-off allowed on an AVB?
  • What does BP+BS stand for?
  • What hazard level is associated with beverage vending or carbonator fixtures?
  • Who must maintain and test preventers on private property?
  • Which backflow preventer screws onto a hose bib?
  • Which scenario is described as a moderate premise hazard?
  • A fire-department pumper or ship-board pump is typically associated with which type of backflow?
  • Back-syphonage is caused by what condition?
  • Which device is not rated for continuous pressure over 12 hours within a 24-hour period?
  • DCVA check-2 hookup?
  • Which statement best describes the AVB sequence in one line?
  • Minor hazard means?
  • After completing an RP relief test using the TV jumper, what is the recommended action?
  • Define a cross connection.
  • Under what conditions can a DCVA be installed in a pit?
  • Air gap vs air break?
  • What hazard does a cross connection pose?
  • In backflow prevention devices, what does PVB stand for?
  • Which factor relates to how likely a hazard will occur?
  • What is used water?
  • When installing a vacuum breaker, where should the submergence mark be placed relative to the flood level rim?
  • DCVA stops backflow and is intended for what hazard level?
  • In a DCVA context, a bleed-off assembly is used to compensate for which condition?
  • DuC is used for what type of hazard and service?
  • Which components make an assembly field-testable?
  • If the RP relief spits intermittently before you close SOV2, what is the most likely cause?
  • Which device uses air gap protection?
  • True or false: willfully causing a cross connection makes you liable for damages.
  • What best describes the TV1-to-TV4 jumper on an RP?
  • The water purveyor is directly responsible to supply potable water to a premise.
  • An air gap near a corner within 4 pipe diameters of two walls requires what adjustment?
  • What is an auxiliary water supply?
  • Unknown substance — what hazard do you assume?
  • Apparent vs actual pressure drop on an RP?
  • What is the best protection for the people inside the building?
  • For the DCVA check-1 hookup, which action should you take first?
  • Lawn irrigation, no chemicals requires which protection?
  • During RP restoration, what is the status of SOV1 before proceeding?
  • Which set lists the four health-hazard classes?
  • Which method of application protects occupants?
  • Degreaser — CSA vs this manual? Which statement best reflects severity and AHJ influence?
  • Name the big four assemblies and what each stops.
  • Not for 12-hour pressure, which statement best describes the AVB/flow relationship?
  • After any repair, what must you do?
  • What is an air gap defined as?
  • According to CSA, if the water line is the electrical ground, what must you do before pulling the valve?
  • Moderate hazard means?
  • Minor hazard is described by which phrase?
  • Which backflow device abbreviation expands to Double Check Valve Assembly?
  • Which devices require a hot-water rating above 43 °C?
  • What are the three CSA degrees of hazard?
  • SRPVB vs PVB — how do they differ?
  • What tool is used to compensate a small leaking SOV1 on a DCVA?
  • If you observe SOV1 not closed or leaking during a DCVA check, which action is most appropriate?
  • Non-continuous pressure is defined as not exceeding how many hours in 24 hours?
  • Premise isolation vs fixture / in-plant isolation?